Fire Door Gaps and Seals: What Property Managers Need to Inspect

On November 28, 2026, Posted by , In Door Solutions, With No Comments

A fire door only holds back fire and smoke while the gaps around it stay tight and its seals stay intact. Many fire doors that fail an inspection look fine from the corridor, because the fault sits within a few millimetres of the edge. Gaps and seals deserve your closest attention on every walk-through, since they’re the first parts to drift out of spec.

Enfant Terrible supplies and installs fire-rated doors for Australian homes and commercial buildings. We’d rather you catch gap and seal faults yourself, well before an inspector writes them up.

Start with the fire door gap requirements Australia applies under AS 1905.1, since every seal check depends on those limits. From there, work through the seal, hardware and record checks below as part of a full door inspection.

Fire Door Gap Requirements in Australia: What AS 1905.1 Allows at the Head, Sides and Floor

Close-up photograph of a technician's hand holding a metal gap gauge

AS 1905.1 is the Australian Standard for fire door installation. The standard caps the clearance between the door and frame, and between the leaf and floor. Smoke and hot gases slip through any gap the seals cannot close, and once that happens, fire compartmentation breaks down.

The table lists the maximum gap for each edge, the usual cause of a wide reading and the fix:

LocationMaximum gapWhat a wider gap usually meansWhat to do
Head (top of the door)3mmSagging hinges or a dropped leafTighten or replace the hinge screws, then measure again
Sides (hinge and lock edges)3mmFrame movement or a warped leafCheck the leaf for twist with a straightedge
Meeting stiles (double doors)3mmLeaves sitting out of lineAdjust the hinges until both leaves close flush
Floor (bottom edge)10mm to the floor finishA floor finish that someone removed or changedMeasure from the finished surface and fit a tested drop seal if needed

Check the compliance tag on the hinge edge before you sign off any door. The manufacturer’s test evidence can set tighter limits for that doorset, and the tested limit overrides the table. Measure every edge with a feeler gauge (a set of thin metal blades), because inspectors want a recorded figure in millimetres.

Inspecting Intumescent and Smoke Seals on Fire Doors

Seals close the spaces that the leaf and frame leave open, and each seal type fails in its own way. Under the National Construction Code (NCC), Specification 12 of NCC 2025 requires smoke doors to stop smoke passing through the doorway. Worn seals are usually the first part to fail those safety requirements.

Intumescent Strips in the Leaf or Frame Rebate

When heat hits an intumescent strip, the strip swells to many times its original size. The swollen strip fills the gap and stops flames curling around the edges of the door. Each strip sits in a groove along the leaf edge or frame rebate. Because the strips work without power or people, they’re a core part of passive fire protection.

Look for strips that have cracked, lifted or gone missing along any length. A single missing section leaves a clear path for heat, even when the rest of the strip looks perfect.

Press each strip with your thumb as you walk the full edge (loose ends often appear near the top hinge). Record the exact location of any damage, then order a replacement strip that matches the door’s tag.

Smoke Seals: Brushes, Fins and the Corners Where They Tear

Smoke seals stop cold smoke, which travels ahead of the heat that activates intumescent strips. Most smoke seals use a brush or a rubber fin that touches the closed leaf along its full length.

Corners usually tear first because the leaf rubs them every time the door closes. Once a corner splits, smoke escapes through the tear into the corridor or stairwell.

To test a smoke seal, close the door and dim the lights on one side. Then have someone point a torch along the edge from the other side. A faint glow through brush bristles can be normal, but a clear line of light means the seal needs replacing.

The Threshold Seal and What Changes When the Floor Finish Does

The threshold seal covers the gap under the leaf. A new floor finish usually changes the floor gap, while everyday wear rarely moves it much. Pulling up carpet to lay tiles or polished concrete can open several millimetres under the leaf in a single weekend.

In strata buildings, owners and tenants often lay new flooring near apartment fire doors without telling the fire contractor. The floor gap can then drift between fire door inspections without anyone noticing.

Ask owners and tenants to send a quick note whenever flooring changes near a fire door. Then measure the floor gap again, and fit a drop seal tested with that doorset if the reading tops 10 mm.

Painted-Over, Patched or Replaced With the Wrong Seal Products

Paint stiffens brush seals and coats intumescent strips, so neither works the way it did in testing. After a quick repaint between tenancies, you’ll often find a smoke seal glued flat against the frame.

Patched or swapped seals are harder to spot. A hardware-store seal might look similar, yet the door’s fire-resistance level (FRL) only covers the seal products tested with that doorset.

Match every replacement seal against the door’s tag or the manufacturer’s records, since a certified fire door keeps its rating only with listed parts. When a door has paint, patches and the wrong seal, check the warning signs a door needs replacing before paying for more repairs.

Detailed side-angle photograph of a fire door's edge showing

What Else Belongs on a Fire Door Maintenance Checklist?

A fire door maintenance checklist also needs the parts that make the door close and latch on its own. Add the compliance tag and the clear space in front of each door to the same list. Thinking about what to add to your rounds? Start with the three checks below on every door you visit.

  • Door Closers and Self-Closing: From fully open, a fire door should swing shut and latch without anyone pushing it. Door closers lose oil and tension over time, so the door slows down and stops short of the latch. Open each door all the way, let go and log each door that fails to latch.
  • Latches and Door Hardware: Loose latches let fire pressure push a closed door back open. Hinges, locks and handles must match the door hardware listed for that doorset, since unlisted parts can void the fire rating. Push on each closed door to test the latch, and note any rattle or play.
  • Tags, Signs and Clear Space: Each door carries a compliance tag that proves its rating to the inspector. A door with a missing tag, no signage or a blocked approach can fail on the spot. Photograph each tag, then remove wedges, bins or stored items as you find them.

Clear wedged-open doors before anything else, because a propped door lets fire and smoke straight through and puts life safety at risk. Tired seals still slow the spread on a closed door, so occupants stay protected while you arrange repairs. Check loading docks and bin rooms on every visit, since wedges tend to reappear there.

Commercial Fire Doors Stay Compliant Through Records, Checks and Sign-Off

Those walk-through findings only count if you record them properly. Two Australian Standards cover fire doors: AS 1905.1 for installation and AS 1851 for maintenance. Commercial fire door compliance depends on how often you check each door and what you record.

For fire and smoke doors, the standard sets six-monthly routine checks and a yearly survey. States apply AS 1851 through their own building fire safety laws, so check which edition your building’s approval calls up.

Records carry the same weight as the checks themselves. The NSW Building Commission owner responsibilities page states that NSW building owners must keep AS 1851-2012 records for at least seven years. Owners must also make the records available for inspection, so a lost logbook becomes a fire safety compliance fault in its own right.

In NSW, an accredited practitioner (fire safety) assesses the building’s fire safety measures, including the doors. The owner then uses the practitioner’s assessment to issue the annual fire safety statement (AFSS). Other states use their own sign-off, such as Victoria’s annual essential safety measures report, so confirm the local requirement. If you manage several buildings, a single missing door report can hold up an entire statement.

A missed inspection round can also stall sign-off, because the practitioner cannot verify each door’s condition for that period. Complete records prevent that hold-up.

Each door record should hold these details:

  • Door location, number and the fire rating on its tag
  • Measured gaps at the head, sides and floor, in millimetres
  • Seal condition, with photos of any damage
  • Repairs made, who carried them out and the date
  • The name and accreditation of the person signing off

Keep one file per door, so the next inspector can follow every fault and fix in order. Start with the gap measurements, since they’re the entry most likely to be missing when a statement falls due.

Low-angle photograph of the bottom of a fire door with a metal gap

Book a Walk-Through Before Your Next Sign-Off

Grab a feeler gauge and a torch before your next six-monthly round, and start with stairwell and exit-corridor doors. Stairwell and exit doors guard the routes occupants use to escape, so fix any faults there before moving on to internal fire doors. Log each reading on the spot, so every door file is complete before the practitioner arrives.

Ready to get every door signed off without surprises? You can book a walk-through with Enfant Terrible for a clear record of each gap, seal and repair before your next statement falls due.